作者(zhe):山東順成電氣(qi)設備(bei)有限公司 發布時間(jian):2022/8/25 20:32:35 瀏覽次數:27
1.電(dian)纜橋(qiao)架安裝時(shi),應首(shou)先設(she)計(ji)選(xuan)型過(guo)程根據各個系統纜線(xian)(xian)(xian)(xian)的類型、數量,選(xuan)擇合理的橋(qiao)架。確(que)定(ding)方(fang)向,應盡(jin)量讓線(xian)(xian)(xian)(xian)路(lu)沿建筑物行進,避免(mian)大(da)跨度(du)(du)空(kong)間穿過(guo),盡(jin)可能避免(mian)線(xian)(xian)(xian)(xian)路(lu)與線(xian)(xian)(xian)(xian)路(lu)或其他腐蝕性管(guan)道交叉。如(ru)需跨度(du)(du)空(kong)間穿行,需提前(qian)計(ji)算好距離和寬度(du)(du),提前(qian)確(que)定(ding)所需要的線(xian)(xian)(xian)(xian)以及(ji)橋(qiao)架。確(que)定(ding)好所用的線(xian)(xian)(xian)(xian)以及(ji)線(xian)(xian)(xian)(xian)橋(qiao)之后,根據安裝場所等的限制條件確(que)定(ding)安裝方(fang)式(shi)。繪制電(dian)纜橋(qiao)架平、刨面圖(tu),特殊(shu)部位還(huan)應有空(kong)間圖(tu),并列出材料表(biao)。
2.在安裝時,如(ru)果電(dian)力電(dian)纜(lan)(lan)橋架(jia)必須(xu)合用(yong)(yong),應將電(dian)力電(dian)纜(lan)(lan)和弱點電(dian)纜(lan)(lan)各(ge)直(zhi)一側,中間(jian)用(yong)(yong)隔板分隔。弱電(dian)纜(lan)(lan)與其它低電(dian)壓電(dian)纜(lan)(lan)合用(yong)(yong)橋架(jia)是,應選擇具有(you)外屏蔽(bi)層(ceng)的系統弱電(dian)電(dian)纜(lan)(lan),一面(mian)彼此間(jian)產生影(ying)響。
3.電纜線橋有室外(wai)進入(ru)室內時(shi),橋架(jia)向外(wai)的(de)(de)坡度不得(de)小于1/100/。電纜橋架(jia)與(yu)用電設備交(jiao)越時(shi),之(zhi)(zhi)間(jian)的(de)(de)凈距離不得(de)小于0.5m。兩(liang)組電纜橋架(jia)在同一高(gao)度平行敷設時(shi),之(zhi)(zhi)間(jian)的(de)(de)凈距離不得(de)小于0.6m。繪圖室應注意精確表明各數據(ju)的(de)(de)值。橋架(jia)水(shui)平敷設時(shi),支撐間(jian)距一般在1.5-3m之(zhi)(zhi)間(jian),垂直(zhi)敷設時(shi)固定在建筑物(wu)構體上(shang)的(de)(de)間(jian)距最好(hao)小于2m。
橋架水平敷(fu)設時,支撐間距一般為1.5-3m,垂(chui)直敷(fu)設時固定(ding)在建(jian)筑物構體上(shang)的間距宜(yi)小于2m。